EN50288-7 Cables
XLPE Insulated, LSZH Sheathed Instrumentation Cables

PE Insulated, PVC Sheathed, Individual & Overall Screened, Armoured Instrumentation Cables (Multitriple)

RE-2Y(St)YSWAY-TiMF 70°C / 300 V

APPLICATION:

EN 50288-7 cables are used for transmission of analogue and digital signals in instrument and control systems;

allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to

low impedance sources, e.g. public mains electricity supply.

Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for

direct buiral. Recommended for use as fire protection messure for people and important material assets.

STANDARDS

RE-2Y(St)YSWAY-TiMF 70°C / 300 V

Basic design to EN50288-7

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)*** EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard, *** denotes optional.

VOLTAGE RATING

300V

CABLE CONSTRUCTION

Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation: PE compound as per EN 50290. 2-23.

Individual Screen: Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned

copper drain wire, 0.5mm²

Pair:Two conductors twisted to form a pair

Lay-up: Pairs laid up in layers of optimum pitch

Separator: Polyester tape

Overall Screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2

Inner Sheath: Thermoplastic PVC compound

Armour: Galvenized round steel wire, EN 10257-1

Outer Sheath: Thermoplastic PVC compound as per EN 50290-2-22. UV resistance, hydrocarbon resistance, oil

resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance

standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound

and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.

Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES

Temperature Range During Operation (Fixed State): -30°C – +70°C

Temperature Range During Installation (Mobile State): -5°C – +50°C

Minimum Bending Radius: 10 X Overall Diameter

Sunlight Resistance: UL 1581 section 1200

Oil Resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile

strength/min.60% of elongation)

Electrical PROPERTIES

Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 115
Inductance mH/km(Max.) 1
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) Operating voltage Urms μH/Ω V V 25 25 25 40 40
300
Test Voltage Core to Core 1500
Core to Screen V 1500

CONSTRUCTION PARAMETERS

 

 

Caledonian Cable Code

RE-2Y(St)YSWAY-TiMF

 

No. of Triples x3xCross Section

 

Nominal Insulation Thick
-ness

 

Nominal Inner Sheath Thick
-ness

Nominal
Overall Diameter Over Inner Sheath

 

Nominal Armour Wire Diameter

 

Nominal Outer Sheath Thick
-ness

 

No.x3xmm2

mm

mm

mm

mm

mm

0.5mm2, Multitriple

RE-2Y(St)YSWAY-TiMF 2T0.5

2x3x0.5

0.35

1.0

9.7

0.9

1.4

RE-2Y(St)YSWAY-TiMF 4T0.5

4x3x0.5

0.35

1.0

11.1

0.9

1.4

RE-2Y(St)YSWAY-TiMF 5T0.5

5x3x0.5

0.35

1.1

12.4

0.9

1.5

RE-2Y(St)YSWAY-TiMF 6T0.5

6x3x0.5

0.35

1.1

14.0

0.9

1.5

RE-2Y(St)YSWAY-TiMF 8T0.5

8x3x0.5

0.35

1.1

14.9

0.9

1.5

RE-2Y(St)YSWAY-TiMF 10T0.5

10x3x0.5

0.35

1.2

17.0

1.25

1.6

RE-2Y(St)YSWAY-TiMF 12T0.5

12x3x0.5

0.35

1.2

17.6

1.25

1.6

RE-2Y(St)YSWAY-TiMF 16T0.5

16x3x0.5

0.35

1.3

20.1

1.25

1.7

RE-2Y(St)YSWAY-TiMF 20T0.5

20x3x0.5

0.35

1.4

22.3

1.25

1.7

RE-2Y(St)YSWAY-TiMF 24T0.5

24x3x0.5

0.35

1.5

24.4

1.25

1.8

0.75mm2, Multitriple

RE-2Y(St)YSWAY-TiMF 2T0.75

2x3x0.75

0.38

1.0

10.6

0.9

1.4

RE-2Y(St)YSWAY-TiMF 4T0.75

4x3x0.75

0.38

1.1

12.4

0.9

1.5

RE-2Y(St)YSWAY-TiMF 5T0.75

5x3x0.75

0.38

1.1

13.7

0.9

1.5

RE-2Y(St)YSWAY-TiMF 6T0.75

6x3x0.75

0.38

1.1

15.4

0.9

1.5

 

 

Caledonian Cable Code

RE-2Y(St)YSWAY-TiMF

 

No. of Triples x3xCross Section

 

Nominal Insulation Thick
-ness

 

Nominal Inner Sheath Thick
-ness

Nominal
Overall Diameter Over Inner Sheath

 

Nominal Armour Wire Diameter

 

Nominal Outer Sheath Thick
-ness

 

No.x3xmm2

mm

mm

mm

mm

mm

RE-2Y(St)YSWAY-TiMF 8T0.75

8x3x0.75

0.38

1.2

16.7

0.9

1.6

RE-2Y(St)YSWAY-TiMF 10T0.75

10x3x0.75

0.38

1.3

19.0

1.25

1.6

RE-2Y(St)YSWAY-TiMF 12T0.75

12x3x0.75

0.38

1.3

19.7

1.25

1.7

RE-2Y(St)YSWAY-TiMF 16T0.75

16x3x0.75

0.38

1.4

22.5

1.25

1.7

RE-2Y(St)YSWAY-TiMF 20T0.75

20x3x0.75

0.38

1.5

24.9

1.25

1.8

RE-2Y(St)YSWAY-TiMF 24T0.75

24x3x0.75

0.38

1.6

27.2

1.25

1.9

1.0mm2, Multitriple

RE-2Y(St)YSWAY-TiMF 2T1.0

2x3x1.0

0.4

1.0

11.5

0.9

1.4

RE-2Y(St)YSWAY-TiMF 4T1.0

4x3x1.0

0.4

1.1

13.4

0.9

1.5

RE-2Y(St)YSWAY-TiMF 5T1.0

5x3x1.0

0.4

1.1

14.8

0.9

1.5

RE-2Y(St)YSWAY-TiMF 6T1.0

6x3x1.0

0.4

1.2

16.9

0.9

1.5

RE-2Y(St)YSWAY-TiMF 8T1.0

8x3x1.0

0.4

1.2

18.1

1.25

1.6

RE-2Y(St)YSWAY-TiMF 10T1.0

10x3x1.0

0.4

1.3

20.7

1.25

1.7

RE-2Y(St)YSWAY-TiMF 12T1.0

12x3x1.0

0.4

1.3

21.4

1.25

1.7

RE-2Y(St)YSWAY-TiMF 16T1.0

16x3x1.0

0.4

1.4

24.4

1.25

1.7

RE-2Y(St)YSWAY-TiMF 20T1.0

20x3x1.0

0.4

1.5

27.1

1.25

1.8

RE-2Y(St)YSWAY-TiMF 24T1.0

24x3x1.0

0.4

1.6

29.6

1.6

1.9

1.3mm2, Multitriple

RE-2Y(St)YSWAY-TiMF 2T1.3

2x3x1.3

0.45

1.1

12.8

0.9

1.5

RE-2Y(St)YSWAY-TiMF 4T1.3

4x3x1.3

0.45

1.1

14.7

0.9

1.5

RE-2Y(St)YSWAY-TiMF 5T1.3

5x3x1.3

0.45

1.2

16.5

0.9

1.6

RE-2Y(St)YSWAY-TiMF 6T1.3

6x3x1.3

0.45

1.3

18.8

1.25

1.6

RE-2Y(St)YSWAY-TiMF 8T1.3

8x3x1.3

0.45

1.3

20.1

1.25

1.7

RE-2Y(St)YSWAY-TiMF 10T1.3

10x3x1.3

0.45

1.4

23.0

1.25

1.8

RE-2Y(St)YSWAY-TiMF 12T1.3

12x3x1.3

0.45

1.5

24.0

1.25

1.8

RE-2Y(St)YSWAY-TiMF 16T1.3

16x3x1.3

0.45

1.6

27.4

1.25

1.9

RE-2Y(St)YSWAY-TiMF 20T1.3

20x3x1.3

0.45

1.7

30.4

1.6

2.0

RE-2Y(St)YSWAY-TiMF 24T1.3

24x3x1.3

0.45

1.8

33.1

1.6

2.0

 

 

 

Caledonian Cable Code

RE-2Y(St)YSWAY-TiMF

 

No. of Triples x3xCross Section

 

Nominal Insulation Thick
-ness

 

Nominal Inner Sheath Thick
-ness

Nominal
Overall Diameter Over Inner Sheath

 

Nominal Armour Wire Diameter

 

Nominal Outer Sheath Thick
-ness

 

No.x3xmm2

mm

mm

mm

mm

mm

RE-2Y(St)YSWAY-TiMF 2T1.5

2x3x1.5

0.45

1.1

13.2

0.9

1.5

RE-2Y(St)YSWAY-TiMF 4T1.5

4x3x1.5

0.45

1.2

15.4

0.9

1.5

RE-2Y(St)YSWAY-TiMF 5T1.5

5x3x1.5

0.45

1.2

17.1

1.25

1.6

RE-2Y(St)YSWAY-TiMF 6T1.5

6x3x1.5

0.45

1.3

19.5

1.25

1.6

RE-2Y(St)YSWAY-TiMF 8T1.5

8x3x1.5

0.45

1.4

21.1

1.25

1.7

RE-2Y(St)YSWAY-TiMF 10T1.5

10x3x1,5

0.45

1.5

24.1

1.25

1.8

RE-2Y(St)YSWAY-TiMF 12T1.5

12x3x1.5

0.45

1.5

24.9

1.25

1.8

RE-2Y(St)YSWAY-TiMF 16T1.5

16x3x1.5

0.45

1.6

28.4

1.6

1.9

RE-2Y(St)YSWAY-TiMF 20T1.5

20x3x1.5

0.45

1.7

31.6

1.6

2.0

RE-2Y(St)YSWAY-TiMF 24T1.5

24x3x1.5

0.45

1.8

34.4

1.6

2.1

Note : Other conductor sizes & core configurations are available upon request.